Arc Flash & Arc Blast
Arc flash is one of the most severe electrical hazards in the workplace. NFPA 70E (Standard for Electrical Safety in the Workplace) governs arc flash hazard analysis, PPE selection, and safe work practices.
What Is an Arc Flash?
An arc flash is an electrical discharge through the air between conductors or between a conductor and ground. It occurs when insulation fails, equipment is damaged, or a conductive object bridges two energized conductors. Temperatures can exceed 35,000°F — nearly four times hotter than the surface of the sun.
Arc Blast
The explosive expansion of air and metal vapor during an arc flash produces an arc blast — a high-pressure shockwave capable of throwing workers across a room, collapsing lungs, and rupturing eardrums. Arc blast is distinct from arc flash thermal burns and must be addressed separately in PPE selection.
Incident Energy
Incident energy is the amount of thermal energy impressed on a surface at a working distance during an arc flash event, measured in calories per square centimeter (cal/cm²). PPE arc ratings must meet or exceed the calculated incident energy for the task.
Arc Flash Boundary
The arc flash boundary is the distance from an arc source at which incident energy equals 1.2 cal/cm² — the onset of a second-degree burn. Workers inside this boundary must wear arc-rated PPE. NFPA 70E requires an arc flash hazard analysis to determine this boundary.
PPE Categories (NFPA 70E)
NFPA 70E Table 130.5(G) defines four PPE categories based on incident energy: Category 1 (4 cal/cm² minimum arc rating), Category 2 (8 cal/cm²), Category 3 (25 cal/cm²), Category 4 (40 cal/cm²). Higher categories require more protective clothing and face protection.
Energized Electrical Work Permit
NFPA 70E requires a written energized electrical work permit when work must be performed inside the restricted approach boundary or on energized equipment above 50V. The permit documents the justification, hazard analysis, PPE required, and approvals.